• thermal-hydraulic tests of a recirculation cooling installation for the rostov nuclear power station

    جزئیات بیشتر مقاله
    • تاریخ ارائه: 1392/07/24
    • تاریخ انتشار در تی پی بین: 1392/07/24
    • تعداد بازدید: 1130
    • تعداد پرسش و پاسخ ها: 0
    • شماره تماس دبیرخانه رویداد: -
     results obtained from thermal-hydraulic tests of the recirculation cooling installation used as part of the air cooling system under the containments of the rostov nuclear power station units 3 and 4 are presented. the operating modes of the installation during normal operation (air cooling on the surface of finned tubes), under the conditions of anticipated operational occurrences (air cooling and steam condensation from a steam-air mixture), and during an accident (condensation of pure steam) are considered. agreement is obtained between the results of tests and calculations carried out according to the recommendations given in the relevant regulatory documents. a procedure of carrying out thermal calculation for the case of steam condensation from a steam-air mixture on the surface of fins is proposed. the possibility of efficient use of the recirculation cooling installation in the system for reducing emergency pressure under the containment of a nuclear power station is demonstrated.

سوال خود را در مورد این مقاله مطرح نمایید :

با انتخاب دکمه ثبت پرسش، موافقت خود را با قوانین انتشار محتوا در وبسایت تی پی بین اعلام می کنم
مقالات جدیدترین رویدادها
مقالات جدیدترین ژورنال ها